Product Name: Analog I/O Module
Model: SA-8801
Analog Input
Channels:
4 channels (configurable as input/output; supports voltage/current)
Type:
Analog Input (Voltage / Current / ADC)
Range:
• Voltage Input: 0–10 V
• Current Input: 4–20 mA
Resolution: 24-bit
Input Impedance / Current Mode:
High impedance in voltage mode; supports internal loop-powered configuration for 4–20 mA input
Overvoltage Protection:
Withstands up to ±40 V (absolute maximum), with ESD protection
Overcurrent Protection:
Maximum 25 mA (DAC current input); supports short circuit (SC) and open circuit (OC) fault flags
Per-Channel Configuration:
Each channel supports independent configuration of mode, range, diagnostics, and power switching (AVDD_HI/LO)
Disconnection Detection:
Supports open/short circuit diagnostics (SC for current input, OC for voltage input) with status flags
Isolation:
External ADuM digital isolator with 2.2 mm isolation gap
Analog Output
Data acquisition method: OpenThread (802.15.4)
Data update frequency:
- Thread: 1 minute
- Local measurement: 0.5 seconds
- Modbus485: 0.5 seconds
Channels:
4 channels (configurable as input/output; supports voltage/current)
Type:
Voltage Output / Current Output / Digital I/O
Range:
• Voltage Output: 0–10 V
• Current Output: 4–20 mA
Resolution:
16-bit DAC
Output Accuracy:
Current Output TUE: ±0.2% FSR
Fault Diagnostics:
Supports open/short circuit detection (OC for current output, SC for voltage output) with channel status flags
Output Capability:Max current output: 20 mA, with current limiting (internal RSENSE); short-circuit protection voltage approx. -120 ~ 240 mV
Power-On Default:Voltage output: 0 V; Current output: 0 mA; ADC inactive (safe default state)
Isolation:X1
Analog Output
Data Acquisition: OpenThread (802.15.4)
Data Update Rate: • Thread: 1 minute
• Local Measurement: 0.5 second
• Modbus RS485: 0.5 second